China 25-500kVA Three Phase Modular Online Large UPS Power Supply, Find details about China UPS Power Supply, UPS from 25-500kVA Three Phase Modular Online Large UPS Power Supply
Features & Application |
System capacity has 150kVA, 250kVA, 500kVA and etc models, power module is 25kVA, users can choose freely according to the load;
System is for modular structure, consist of static switch module, monitoring module and N power module in parallel, module N + X redundancy, can proceed online expansion according to user requirements;
Monitor module, static switch module and power module can be online hot plug; System can be setted to 1/1, 1/3, 3/1 or 3/3 come into and outgoing line way as requirements;
Adopt master-slave parallel, multi-stage distributed control technology, no operation bottleneck, reliable performance;
All power module share battery pack, has perfect battery management function: Battery has self-discharge function, automatic floating conversion function, temperature compensation, automatic flow function;
Any power module has the balance of input, output, and charging power distribution function;
AC input adopt continuous current mode (CCM) to operate, reduce power interference (RFI/EMI);
Shape structure meet the requirements of the industry standard, equipment is small volume, light weight, can meet the ordinary building bearing requirements;
Optional input and output isolation transformer K values
Maintenance manual switch, C grade lightning protection module.
UPS can be used in parallel, the maximum 4 PCS parallel to reach the expand demand.
Key Feature
·Module structure, UPS capacity can be changed based on loads
·N+X redundancy
·Efficiency of UPS is more than 96%, environmental protection
·Friendly interface design of LCD
·Microprocessor control, self-check, battery check by itself
·Online static bypass, strong protection for overload and UPS fault
·RS232 & SNMP for optional, provide remote control management
·Intelligent temperature controlled fan, long life and low noise
·MTBF is more than 200, 000 hours, and MTTR is 20 minutes
Technical Performance |
3RW (M25) System Technical Specification
Model | 3RW-150 | 3RW-250 | 3RW-500 | ||
Max Capacity | 150KW | 250kVA | 500kVA | ||
Power Module | Type of power module | M25(M20 for optional) | |||
Mains Input | Input mode | Three Phase Four Wire+ Ground/Single Phase Two Wire+ Ground | |||
Input voltage | 380V/220V±20%, 400V/230V±20%, 415V/240V±20% | ||||
Input Frequency | 50Hz±10%, 60Hz±10% | ||||
Soft Start(Sec. ) | 60sec | ||||
Input Total Harmonic Distortion THD(%) | <3% | ||||
Input PF | ≥0.99 | ||||
Input Bypass | Input Voltage | 380V/220V±20%, 400V/230V±20%, 415V/240V±20% | |||
Input Frequency | 50Hz±4%, 60Hz±4% | ||||
Input frequency tracking range | 50Hz±4%, 60Hz±4% | ||||
DC Input | Rated Input Voltage | ±384VDC | |||
Input voltage range | ±345V~±440V DC | ||||
Charge Characteristic | Charging current limited | Yes | |||
Charging Time | 10 hours(2 hours backup battery capacity) | ||||
Charging Voltage Stability | ±1% | ||||
Output | UPS Power Factor | 0.9 | |||
Output Voltage | 380V/220V AC, 400V/230V AC, 415V/240V AC | ||||
Output Frequency | 50Hz±4%; Mains overrun or battery mode output is 50Hz±0.2% 60Hz±4%; Mains overrun or battery mode output is 60Hz±0.2% | ||||
Output voltage Stability | 380V/220V±1%(Static); 380V/220V±2%(Load change from 0 ~ 100% ) 400V/230V±1%(Static); 400V/230V±2%(Load change from 0 ~ 100% ) 415V/240V±1%(Static); 415V/240V±2%(Load change from 0 ~ 100% ) | ||||
Output voltage recovery time | <20ms(Load change from 0 - 100% ) | ||||
Overload | Rated Load 125%, Runs 10min | ||||
Mains to Battery Transfer Time | 0ms | ||||
Bypass to Inverter Transfer Time | <1ms | ||||
Crest Factor | 3: 1 | ||||
Output Total Harmonic Distortion THD(%) | ≤1%(Linear load ) ≤3%(Non Linear Load) | ||||
Efficiency | ≥95%(AC Power Supply) ≥98%(Battery Power Supply) | ||||
Flow Accuracy | ≤5% | ||||
Working Environment | Storage Environment Temperature | -25ºC~60ºC | |||
Working Environment Temperature | -5ºC~40ºC | ||||
Elevation Allowed | ≤1500 Meters | ||||
Humidity | ≤95% (no condensing) | ||||
IP Class | IP30 | ||||
Cooling | Air | ||||
Safety Standard | EN62040-1-1: 2003 IEC60950-1: 2001 | ||||
Electromagnetic Compatibility Characteristics | EN62040-2: 2006 | ||||
Noise | ≤55dB | ||||
Others | Dimension(H×W×D)mm Weight Kg | 600*800*1600 about 230KG | 800*800*2000 about 260KG | 2000*800*2000 about 660KG | |
Structure | 19 inch Standard | ||||
Monitor Management System | UP Supervisor | ||||
RS232, RS485/422 and configure 8PCS dry contacts | Standard | ||||
TCP/IP Expansion CARDS | Standard | ||||
Display | LCD/LED |
Module Model | M25(M20/M30 for optional) |
Module Capacity | 25kVA |
Input/Output Way | Three phase in three phase out, three phase in single phase out, single phase in three phase out, single phase in single phase out |
Module Dimension(H×W×D)mm | 133×482×465 |
Weight(kg) | About 21 kg |
Charging module specification | Each module can supply 6 kw charging power |
Input PF | ≥0.99 |
Overload | 135% |
Max Cooling Power | 1190W |
Input Total Harmonic Distortion THDI(%) | ≤3% |