China on-Site and in Laboratory Portable Voltage Transformer Analyzer, Find details about China Voltage Transformer Analyzer, Portable Voltage Transformer Analyzer from on-Site and in Laboratory Portable Voltage Transformer Analyzer
As a manufacturer or testing lab you can use GF1061PT in your production facilities and test/development labs. it can finish the measurements (M) and protection (P) class PT. Adopt 7 inch touch TFT color LCD, self-equipped mini type printer supporting field printing; supporting to use USB flash disk to dump data. The GF1061PT portable PT tester is the most complete and easy-to-use testing system for PTs according to IEEE and IEC standards.
The GF1061PT Transformer Analyzer measures current transformer (CT) admittance, CT ratio, CT primary-to-secondary phase angle and the voltage, current and phase angle of the service. With the 'Burden CT/PT Option', it determines the CT secondary burden capability, the regulation of the potential transformer (PT) and its secondary burden capability and provides for CT core demagnetization.
High quality CT PT analyzer for current transformer testing, AC output voltage 220V, frequency 50Hz, measurement accuracy ±0.02%, with advanced design, stable and reliable product performance, complete functions, high degree of automation and high test efficiency.
I. Voltage transformer (PT) |
---|
1. Excitation characteristic test |
2. Transformation ratio test |
3. Polarity |
4. Ratio error, phase error |
5. Degauss |
6. Calculation of knee point value |
7. Actual secondary load test (burden test) |
8. Resistance test |
Electrical parameters | ||
---|---|---|
Accuracy | 0.02% | |
Power supply | AC 220V±10% or AC 120V±10%, 50/60Hz or Battery | |
Output voltage | 0-100Vrms | |
Output current | 0-5Arms (20A peak-value) | |
Output power | 0-400 VA (1500 VApeak) | |
Automatic frequency variation range | 0.1-60Hz | |
Equivalent excitation voltage | ≤5000V/50KV | |
Accuracy | ≤0.5% | |
Secondary winding DC resistance measurement | Range | 0.1-1000Ω |
Accuracy | ≤0.05% | |
Secondary actual load measurement | Range | 5VA-1000VA |
Accuracy | ≤0.5%±0.1VA | |
PT phase error measurement | Accuracy | ±1min (typical) / 3 min (guaranteed) |
Resolution | 0.1min | |
PT ratio error measurement | Range | 1-15000 |
Accuracy | ≤0.05% | |
LCD display | 7' inch TFT touch color LCD | |
Communication port | USB port | |
Printer | Yes, Thermal printer | |
Standards | ||
Reference standards | GB1207-2006, GB1208-2006, GB16847-1997 IEC60044-1, IEC60044-6, IEC61869, ANSI/IEEE C57.13 | |
Safety standards | GB 4793.1-2007 | |
EMC | EMC standard 89/336/EEC | |
FCC Subpart B of Part 15 Class A | ||
IEC 1000-4-2/3/4/6 | ||
Mechanical parameters | ||
Overall dimension (L x W x H) (mm) | 280 x 250 x 160 | |
Weight (kg) | ≤4.8 | |
Environmental conditions | ||
Relative humidity | Relative humidity 5%-95% not condensing | |
Operating temperature | -10°C to +50°C | |
Storage temperature | -20°C to +70°C | |
Altitude | ≤1000m |