China Gdva-404 Automatic Current Transformer CT Vt Analyzer, Find details about China Current Transformer Analyzer, CT Analyzer from Gdva-404 Automatic Current Transformer CT Vt Analyzer
1 | Test standards | IEC60044-1, IEC60044-6, GB1208, GB16847, C57.13 |
2 | Power supply | AC220V±10% , 50Hz/60Hz±10% |
3 | Power output | 0.1~180V (AC) |
4 | Current output | 0.001~5A(RMS) |
5 | Power output | 300VA |
6 | Maximum knee voltage measurement | 45kv |
7 | Current measurement | Range:0~10A (automatically change range in 0.1/0.4/2/10A) |
Error <±0.1%+0.01%FS | ||
8 | Voltage measurement | Range:0~200 V (automatically change range in 1V/10V/70V/200V) |
Error < ±0.1%+0.01%FS | ||
9 | Turns ratio measurement | Range :1~35000, |
1~2000 error<0.05% | ||
2000~5000 error>0.1% | ||
5000~35000 error<0.2% | ||
10 | Phase measurement | error : ±2min , resolution : 0.01min |
11 | Coil resistance measurement | Range:0~8kΩ (automatically change range in 2ohm/20ohm/80ohm/800ohm/8kohm) |
Error< 0.2%RDG+0.02%FS | ||
Maximum resolution:0.1mΩ | ||
12 | Temperature measurement | -50~100 Celsius degree , error<3 Celsius degree |
13 | CT Secondary burden | Range 0~160ohm (automatically change range in 2ohm/20ohm/80ohm/160ohm) |
Error <0.2%RDG+0.02%FS | ||
Maximum resolution 0.001ohm | ||
14 | PT Secondary burden | Range 0~80kohm (automatically change range in 800ohm/8kohm/80kohm) |
Error <0.2%RDG+0.02%FS | ||
Maximum resolution: 0.1ohm | ||
15 | PT ratio measurement | Range :1~35000, |
1~5000 error<0.2% | ||
5000~35000 error<0.5% | ||
16 | Saved data groups | >1000groups |
17 | Work condition | Temperature : -10 °C~ 50 °C, moist :≤ 90% |
18 | Size | 485mm×356mm×183mm |
19 | Weight | <15Kg |