China Commercial Wall Mounted Split Air Conditioner Fan Coil, Find details about China Fan Coil, Air Conditioner from Commercial Wall Mounted Split Air Conditioner Fan Coil
Model | HFP02 | HFP03 | HFP04 | HFP05 | HFP06 | HFP08 | |||
Power supply | 220V,50Hz,1Ph | ||||||||
Air volume | H | m³/h | 340 | 510 | 680 | 850 | 1020 | 1360 | |
M | 260 | 380 | 515 | 660 | 765 | 1010 | |||
L | 180 | 260 | 340 | 430 | 520 | 700 | |||
Static pressure | Pa | 0 | 0 | 0 | 0 | 0 | 0 | ||
Cooling capacity | TH | H | W | 2100 | 2700 | 4000 | 4500 | 5700 | 7200 |
SH | W | 1600 | 2025 | 3000 | 3375 | 4300 | 5400 | ||
TH | M | W | 1700 | 2214 | 3200 | 3690 | 4600 | 5904 | |
SH | W | 1399 | 1399 | 2200 | 2409 | 3200 | 3926 | ||
TH | L | W | 1300 | 1647 | 2400 | 2745 | 3500 | 4392 | |
SH | W | 700 | 960 | 1500 | 1715 | 2200 | 2710 | ||
Heating capacity | H | W | 3100 | 4050 | 5900 | 6750 | 8500 | 10800 | |
M | W | 2500 | 3219 | 4700 | 5366 | 6800 | 8586 | ||
L | W | 1700 | 2268 | 3300 | 3780 | 4800 | 6048 | ||
Noise | H | dB(A) | 39 | 41 | 42 | 45 | 46 | 47 | |
Power input | H | W | 35 | 40 | 75 | 90 | 125 | 130 | |
Water flow | H | m³/h | 0.36 | 0.46 | 0.71 | 0.77 | 0.98 | 0.93 | |
Pressure drop | kPa | 12 | 14 | 17 | 18 | 23 | 23.5 | ||
Water pipe in/out | ZG1/2'' | ZG1/2'' | ZG1/2'' | ZG1/2'' | ZG1/2'' | ZG1/2'' | |||
Condensing water pipe | ZG1/2'' | ZG1/2'' | ZG1/2'' | ZG1/2'' | ZG1/2'' | ZG1/2'' | |||
Coil | / | Hydrophilic aluminum fin and copper tube | |||||||
Max working pressure | MPa | 1.6 | 1.6 | 1.6 | 1.6 | 1.6 | 1.6 | ||
Dimension | L×W×H | mm | 780×276×202 | 780×276×202 | 950×313×240 | 950×313×240 | 1055×313×240 | 1055×313×240 | |
Net weight | kg | 10 | 10 | 14 | 14 | 16 | 16 |