China Waterproof 4-20mA DC Output Integrator for Flexible AC Current Probe S9.4, Find details about China Flexible CT Rogowski Coil Sensor PLC Integrator, 4-20mA DC Output Rogowski Coil Integrator from Waterproof 4-20mA DC Output Integrator for Flexible AC Current Probe S9.4
Advantage • High read accuracy 0.5% • Smart volume for limited space installation • Low power consumption • IP68 Related Products Y-FCT,MRC,NRC | Applications Measuring devices • Power meter measurement • Harmonics and transients monitoring • Welding machine control • High current measurement • PLC control |
Model | S9.4 | S9.41 |
Rated output | 4-20mA DC | 333mV |
Maximum Output(overload) | 25mA DC | 4.5V peak |
Output Ripple factor | Default 5% (relay to Response time) | 1% |
Response time | Default 100ms(adjustable) | ≤1us |
Power consumption | 100mW | 70mW |
Bandwidth | 30Hz to 1kHz | 10Hz to 10kHz |
Power supply | 12V or 24V DC | 12V or 24V DC |
Rated Input | 100A 600A 1000A 3000A 6000A | |
Output Wire | 0.5 meter 4pcs wires (RED:power+, GREEN:GND,YELLOW:output +,BLUE:GND) | |
Read Accuracy | 1% typical at 1%(≥10A) to 200% of rated Current @25ºC | |
Phase error | ≤0.5° | |
Linearity | ±0.2% of reading(1% to 200% of range) | |
Minimum Current measurement | 1A (Ripple 100mA) | |
Temperature drift | 200ppm/ºC | |
Weight | 20g | |
Dimension | 53*38*25mm | |
Operating temperature | -20ºC to 70ºC | |
Storage temperature | -30ºC to 90ºC | |
Relative humidity: | 80% max.without condensation | |
Protection degree: | IP68 | |
Other requirements, please contact us to OEM. |
Coil Model | Coil diameter (mm) | Output ratio and tolerance | Signal cable length |
Code:Y-FCT | Code:200(Typical rated 500A) Code:350(Typical rated 1500A) Code:510(Typical rated 3kA) Code:800(Typical rated 10kA) Y-FCT code is length. | Code:110 110mV/kA@50Hz±5% Code:100 100mV/kA@50Hz±0.5% Code:85 85mV/kA@50Hz±0.5% Code:50 50mV/kA@50Hz±0.5% | Code:-2m Code:-5m Code:-10m Code:-20m |
Code:NRC | Code:100(Typical rated 1kA) Code:150(Typical rated 3kA) Code:200(Typical rated 6kA) | ||
Code:MRC | Code:16(Typical rated 100A) Code:24(Typical rated 300A) Code:36(Typical rated 600A) | Code:60 60mV/kA@50Hz±5% Code:50 50mV/kA@50Hz±0.5% | |
Code:SRC | Code:50 Code:100 Code:150 | Code:360 360mV/kA@50Hz±5% Code:333 333mV/kA@50Hz±0.5% Code:100 100mV/kA@50Hz±0.5% Code:85 85mV/kA@50Hz±0.5% Code:50 50mV/kA@50Hz±0.5% | |
Other requirement could be OEM |
Integrator | Output form | Output value | Rated current | Power supply |
Code:D1 (DIN-RAIL integrator) | Code: .1(AC voltage output) Code: .2(DC voltage output) | Code: -333(333mV) Code: -1(1V) Code: -5(5V) | Code: -600A Code: -1kA Code: -3kA Code: -6kA | Code: -12(12V DC) Code: -24(24V DC) |
Code: .3(4-20mA output) | N/A | |||
Code:S9 (mini integrator) | Code: .1(AC voltage output) Code: .2(DC voltage output) | Code: -333(333mV) Code: -1(1V) Code: -3(3V) | Code: -12(6-12V DC) Code: -24(24V DC) | |
Code:S1 (high accuracy integrator) | Code: .1(AC voltage output) Code: .2(DC voltage output) | Code: -333(333mV) Code: -5(5V) Code: -10(10V) | Code: -12(4-12V DC) Code: -24(24V DC) | |
Code: .3(4-20mA output) | N/A | |||
Code:ATP-01 (1A output three phase integrator) | N/A(0-1A) | N/A | Code: -12(12V DC) Code: -24(24V DC) | |
Code:A01 (1A output integrator) | N/A(0-1A) | N/A | N/A(85-265V AC DC) | |
Code:A05 (5A output integrator) | N/A(0-5A) | N/A | N/A(85-265V AC DC) | |
Code:HF (high frequency integrator) | N/A(0-10VAC peak) | N/A | Code: -1kA(1kA/1V) Code: -10kA(10kA/1V) | N/A(4-12V DC) |
Other requirement could be OEM |