Rubber Insulated Flexible Cable Voltage H07rn-F

China Rubber Insulated Flexible Cable Voltage H07rn-F, Find details about China Rubber Insulated Cable, H07rn-F from Rubber Insulated Flexible Cable Voltage H07rn-F

Model NO.
H07RN-F
Material Shape
Round Wire
Range of Application
Mine
Certification
ISO9001, CE, CCC
Brand
Yifang
Standard
DIN VDE 0282-4/2005
Trademark
YIFANG
Transport Package
Treated Drums
Specification
2.5MM2 4MM2
Origin
China
HS Code
8544492100
Model NO.
H07RN-F
Material Shape
Round Wire
Range of Application
Mine
Certification
ISO9001, CE, CCC
Brand
Yifang
Standard
DIN VDE 0282-4/2005
Trademark
YIFANG
Transport Package
Treated Drums
Specification
2.5MM2 4MM2
Origin
China
HS Code
8544492100

RUBBER INSULATED FLEXIBLE CABLE VOLTAGE 450/750V

 

H07RN-F (A07RN-F) 12x2.5 and 7x2.5

 

Application

 

 

For general use in dry, humid and wet locations, for outdoor use, for agricultural applications or in locations subject to explosion hazards. Also suitable for connections of industrial and workshop electrical equipment submitted to medium-level mechanical stress. It can be used for fixed installations in temporary buildings as well as for connections of mobile machines and hoists.

 

Global data

 

 

Brand : YIFANG

 

 

Standard:  DIN VDE 0282-4/2005

 

 

Design features

 

 

ConductorCopper tinned, Fine wire, class 5 according to IEC 60228
Insulation

Ethylene Propylene Rubber (EPR), EI4 Grade

Number code according to VDE 0282-4/2005

Outer SheathChlorinated Polyethylene (CPE), EM2 Grade
Marking

(Year of manufacture) Yifang Cable A07RN-F (number of cores) x (cross-section) CU/EPR/CPE (rated voltage)

 

Electrical parameters

 

Rated Voltage (U0/U) : 450/750 V

High Voltage Test : 2.5kV

 

 

Thermal parameters

 

 

Max. permissible temperature at conductor ≥60 °C

 

Max. short circuit temperature of the conductor 250 °C

 

 

 

 

Environment Condition

 

Oil and weather Resistant, mechanical stress

Flame-retardant

 

 

 

No.DescriptionUnitDataData
1Reference standard VDE 0250,Part 812
2Rated VoltagekV450/750450/750
3Sizemm27x2.512x2.5
4Conductor   
Nominal Cross-section Areamm22.52.5
Max. Stranding Wire Diametermm0.260.26
Max. Diameter of Conductormm2.42.4
Max.D.C Resistance at 20 ºCΩ/km8.218.21
5Insulation   
Nominal thicknessmm0.90.9
Color of insulation--Black with white numbers except Yellow-green ground core
7Outer Sheath   
Nominal thicknessmm2.73.1
Color of sheath--YellowYellow
8Approx. Overall Dia. of cablemm17.7~21.720.6~26.2
9Approx. Weightkg/km8901390
10

Minimum Bending Radius

for installation

--

≤5D (D:overall diameter )(Fixed )

≤10D (D:overall diameter )(Flexible)

11Standard Packing Lengthm10001000