China Air Insulation Electrical Switchgear Ring Main Unit, Find details about China Sf6 Indoor Load Break Switch, Ring Main Unit from Air Insulation Electrical Switchgear Ring Main Unit
Rated voltage (kV) | 7.2 | 12 | 17.5 | 24 | |
Insulation level | |||||
50 Hz, 1 mn (kV rms) | Insulation | 20 | 28 | 38 | 50 |
Isolation | 23 | 32 | 45 | 60 | |
1.2/50μs (kV peak) | Insulation | 60 | 75 | 95 | 125 |
Isolation | 70 | 85 | 110 | 145 | |
Breaking capacity | |||||
Transformer off load (A) | 16 | ||||
Cables off load (A) | 31.5 | ||||
Short-time withstand current (kA.1 s) | 25 | 630 - 1250 A | |||
20 | 630 - 1250 A | ||||
16 | 630 - 1250 A | ||||
12.5 | 400 - 630 - 1250 A | ||||
The making capacity is equal to 2.5 times the short-time withstand current. * 60 kV peak for the CRM unit. | |||||
Maximum breaking capacity | |||||
Rated voltage (kV) | 7.2 | 12 | 17.5 | 24 | |
Units | |||||
IM, IMC, IMB, NSM-cables, NSM-busbars | 630 A - 800 A* | ||||
PM, QM, QMC, QMB | 25 kA | 20 kA | |||
CRM | 10 kA | 8 kA | |||
CRM with fuses | 25 kA | ||||
SF6 circuit breaker range: | |||||
DM1-A, DM1-D, DM1-W, DM1-Z, DM1-S, DM2 | 25 kA | 20 kA | |||
Vacuum circuit breaker range: | |||||
DMV-A, DMV-D, DMV-S | 25 kA | 20 kA |