Micro PLC PR-14 series (Expandable Range)series overview:
PR-14 range(Micro PLC) is advanced level model, incorporating a good mix of digital and Analogue IO, Integrated High Speed inputs and PWM output,clock with calendar, counters , timers , integrated keypad display, serial communications and an expansion port. Available in 120V/240VAC or 12V/24VDC versions ; Easy to configure with drag-and-drop function blocks using FREE xLogicSoft software. Program capacity has been enlarged to 512 function blocks as well, also high-speed count reaches 60KHZ.
PR-14 range offers 4-line*16 characters LCD display and keypad for program modification or display and control whilst program is running. An expansion port allows the connection of up to 16 expansion modules, extending the I/O channel count. Now it is also possible to use the analog output module to solve simple closed-loop control tasks.
Heating and cooling systems can be designed with the RTD PT100 module using special functions for PI control,ramp response and analog multiplexer.
Highlight of PR-14 Series
#70 ready-to use functions integrated-no additional devices such as operating hours counter required.
#Extremely large program capacity:up to 512 functions possible.
#10 digital inputs(incl 6AI with 12/24V DC)and 4 digital outputs on board.
#Flexibly expandable up to 138DI,132DO,72AI,and 32AO.
#Display of message texts,actual and set-point values and direct modification of the values on the display(not on pure variants).
#Integrated data retentivity-ensures backup of the current values in the event of a power failure.
#Customizable Start-up page/screen.
#Bool function,multiple timers,counters,PWM,PI controller,Ramp.Analog math supported.
#Can be modularly expanded up to 270 I/Os.
#230V units can be expanded with analog modules.
#Data-logging:Data from the production process can be saves in SD card of the external accessory called ELC-MEMORY to either read it with a PC or evaluate it from the SD card at the workstation.
#Extremely simple software
#Display of up to 128 messages.
#Multiple kinds of registers can be accessed.
#Parameters setting menu in LCD panel.
#Parameters can be modified in the alarming message.
#Modbus RTU/ASCII protocol supported.
#Retentive memory capability.
#Powerful communication capability(1RS232 port,2 RS485 port and 1 expansion port)
#Password protection.
#It's optional for xLogic to act as salve or master in certain Modbus communication network.
#Backup at Real Time Clock(RTC) at 25 ºC:20 days.
#Communicate with third party device which supports Modbus network.
Technical Specifications:
GENERAL SPECIFICATIONS
Timers : 512
Counters : 512
Function Blocks: 512
Operation temp.: -20ºC-55ºC
Storage:-40ºC-70ºC
Protection: IP20(Non-waterproof)
RTC accuracy : MAX ±2S/day
RTC Backup at 25 °C: 20 days
Program and settings Backup :10 years
Data Power-off retentivity: 10 years
Modify parameters via keypad LCD: yes
Dimensions: 95*90*55(Unit:mm)
Certificate: CE
Installation: 35-DIN rail or screw for installation
Expansion capacity: 16 modules (PR-E-16)
Password protection : 4-digit number password protection or disable program upload function
Communication interface : 1 RS232 port & 2 RS485 port(1 built-in)
Communication protocol : Modbus RTU/ASCII
Technical Index
Power supply: | |
Nominal voltage | DC 12-24V |
Operating limits | DC 10.8-28.8V |
Immunity from micro power cuts | Typ.5 ms |
Max. Startup current | Max. 0.25A |
Max. absorbed power | 3.5 W (10.8V dc) ; 4 W (28.8V dc) |
Protection against polarity inversions | Yes |
Input parameters: | |
Input No | 10 ( I1-IA ) |
Digital input | 10 ( I1-IA ) |
Analogue input | 6 ( I1-I6)(0..10V DC) |
Digital inputs( I7-IA ) | |
Input voltage | DC0-28.8V |
Input signal0 | < 5V DC; <1mA |
Input signal1 | > 8 V DC;>1.7mA |
Input current | 2.3mA @ 10.8V dc 2.6mA @ 12.0 V dc 5.2 mA @ 24 V dc 6.3 mA @ 28.8 V dc |
Response time | 0 to 1 :<1 ms ;1 to 0 :<1 ms |
Maximum counting frequency | 60k Hz(I7--IA) |
Sensor type | Contact or 3-wire PNP |
Input type | Resistive |
Isolation between power supply and inputs | None |
Isolation between inputs | None |
Inputs used as digital inputs( I1-I6 ) | |
Input voltage | DC0-28.8V |
Input signal0 | < 5V DC;<0.1mA |
Input signal1 | > 8 V DC;>0.3mA |
Input current | 0.4mA @ 10.8V dc 0.5mA @ 12.0 V dc 1.2mA @ 24 V dc 1.5mA @ 28.8 V dc |
Response time | 0 to 1 :Typ. 1.5 ms ;1 to 0 :Typ. 1.5 ms |
Maximum counting frequency | Typ.:4 HZ |
Sensor type | Contact or 3-wire PNP |
Input type | Resistive |
Isolation between power supply and inputs | None |
Isolation between inputs | None |
Inputs used as analog inputs( I1-I6 ) | |
Measurement range | DC 0---10V |
Input impedance | Min, 24KΩ ; Max. 72KΩ |
Input voltage | 28.8 V DC max |
Resolution | 10bit ,0.01V |
Accuracy at 25 °C | ± (Max.0.02)V |
Accuracy at 55 °C | ± (Max.0.04)V |
Isolation between analog channel and power supply | None |
Cable length | 10 m max. shielded and twisted |
Output parameters: | |
Output No. | 4 (Q1-Q4) |
Output type | Relay output |
Continuous current | Resistive load 10A/Inductive load 2A |
Max. breaking voltage | AC 250 V DC 110 V |
Max. Allowable Power Force | 1250VA 300W |
Electrical durability Expectancy | 105 Operations at Rated Resistive Load |
Mechanical life | 107 Operations at No Load condition |
Response time | Operate Time : 15 mSec. Max. Release Time : 10 mSec. Max. |
Built-in protections | Against short-circuits: None Against overvoltages and overloads: None |
Switch frequency: | |
Mechanism | 10Hz |
Resistor/light load | 2Hz |
Sensitive load | 0.5Hz |
Other parameters: | |
Weight | Approx.400g |
PR-14 Series CPU | ||||||||
Model | Supply volt | Inputs | Outputs | High-speed count | PWM | HMI | RTC | G.W(g) |
PR-14AC-R | AC110~240V | 10 Digital | 4 relays(10A) | None | NO | YES | YES | 400g |
PR-14DC-DA-R | DC12V-DC24V | 6 digital/analog +4 digital | 4 relays(10A) | 4 routes | NO | YES | YES | 400g |
Dimension&Wiring