China 0-50mv to 0-10V Isolation Amplifier Converter DIN Rail-Mounted, Find details about China 0-50mv to 0-10V, 0-50mv to 0-10V Conditioner from 0-50mv to 0-10V Isolation Amplifier Converter DIN Rail-Mounted
Continuous Isolation Voltage 3KVDC/rms |
Power supply Volt. Input Range: ±25%Vdd |
Operating Temperature - 45ºC ~ + 85ºC |
Wielding Temperature (<10S) +300ºC |
Voltage Signal Output Min. Load 2KΩ |
Parameters | Test Conditions | Min. | Typical Value | Max. | Unit | ||
Isolation voltage | AC,50Hz,1min | 3000 | V(rms) | ||||
Gain | 1 | V/V | |||||
Gain temp. drift | 35 | ppm/ºC | |||||
Non-linearity | 0.1 | 0.2 | %FSR | ||||
Signal Input | Voltage | 0 | 15 | V | |||
Current | 0 | 30 | mA | ||||
Input offset voltage | 2 | 5 | mV | ||||
Input impedence | Voltage | 1 | M | ||||
Current | 50 | 250 | Ω | ||||
Signal output | Voltage | -10 | 10 | V | |||
Current | -20 | 20 | mA | ||||
Load capacity | Voltage | Vout=10V | 2 | kΩ | |||
Current | 0 | 350 50 | 650 | Ω | |||
Frequency response | -3DB | 1 | KHz | ||||
Signal output ripple | No filtering | 10 | 20 | mVRMS | |||
Signal voltage temp. drift | 0.2 | mV/ºC | |||||
Auxiliary power | Voltage | User-defined | 3.3 | 12 | 24 | VDC | |
Consumption | 0.5 | 1 | W | ||||
Operating ambient temp. | -45 | 85 | ºC | ||||
Storage Temp. | -55 | 105 | ºC |
Output | Output load capacity | Response time |
4-20mA | ≤350Ω (If the 650Ω load is required, please notify us) | <1mS |
0-±20mA | ||
0-±5V | > 2KΩ | |
0-±10V | ||
1-5V |