China Automatic DIN Rail Adjustable Over Under Voltage Protector 220VAC, Find details about China Over Voltage Under Voltage Protector, Automatic Reclosing Circuit Breaker from Automatic DIN Rail Adjustable Over Under Voltage Protector 220VAC
Specification
Rated voltage | AC220V 50Hz/60Hz |
Power consumption | <3W |
Supply voltage | AC140V~320V |
When the voltage current is normal the product will Automatic reconnect.
Leakage range: 10~99mA(adjustable)(Default 30mA) Leakage response time: ≤0.1S
Over voltage range: AC250~300V(adjustable)(Default 270V) Overvoltage response time: ≤0.1S
Low voltage range: AC150~190V(adjustable)(Default 170V) Low voltage response time: ≤0.1S
Over current range: 1~63A (adjustable) (Default 40A) Overcurrent range response time: ≤0.1S
Short-circuit current: ≥31ln Short-circuit response time: ≤0.1S
Error in real-time current, voltage and leakage current: ≤5%
Main technical parameters
Rated voltage: AC220V 50Hz/60Hz
Power consumption: <3W
Supply voltage: AC150V~300V
Leakage range: 10~99mA Leakage response time: ≤0.1S
Overvoltage range: AC250~300V Overvoltage response time: ≤0.1S
Low voltage range: AC150~190V Low voltage response time: ≤0.1S
Overcurrent range: 1~63A Overcurrent range response time: ≤0.1S
Short-circuit current: ≥31ln Short-circuit response time: ≤0.1S
Error in real-time current, voltage and leakage current: ≤5%
Max. failure records: 999
Working conditions:
Temperature: -20°~55° Storage temperature: -45°~80°
Humidity: ≤95%Rh Atmospheric pressure: 70kPa~106kPa
Volume: 106X92X70mm
Wiring:you don't need to connect to GND, if you don't have GND
Note 1: This switch cannot be used as a master breaker. Please install a miniature circuit breaker as an overload short-circuiting fitting in front of the switch.
Note 2: Please adjust the current after installation.
Note 3: This product is designed without isolation function. Please disconnect the front breaker before repairing the circuit.
Product Display
Any requirements or question,welcome to "Send" us an e-mail Now!!!