China Online UPS Rack /Tower Convertible Eaton 9sx 20kVA 9sx20kpm, Find details about China Eaton UPS, Single Phase UPS from Online UPS Rack /Tower Convertible Eaton 9sx 20kVA 9sx20kpm
Product Snapshot | |
---|---|
Power Rating | 15 - 20kVA |
Voltage | 1 phase 220/230/240V; 3 phase 380/400/415V |
Frequency | 50Hz / 60Hz |
Topology | Double conversion |
Configuration | Rack / Tower Convertible |
UPS Models | |||
---|---|---|---|
Part Number | Power Rating | Input Plug | Output Receptacles |
(VA/Watts) | |||
Eaton 9SX Rack/Tower | |||
9SX15KPM | 15000 / 15000 | Hardwired | Hardwired |
9SX20KPM | 20000 / 20000 | Hardwired | Hardwired |
General | |
Topology | Double conversion |
Configuration | Rack/Tower |
Part Number | 9SX20KPM |
Rating (VA/Watts) | 20000/20000 |
Dimensions (H x W x D, mm) | 129 x 438 x 589 |
Weight (kg) | 23.7 |
Warranty | 1 year |
Electrical Input | |
Connection | Hardwired - see manual for terminal block layout |
Input Voltage Range | 160V~300V full load; 100~160V linear derating |
Nominal Voltage | 1 phase 220/230/240V; 3 phase 380/400/415V |
Frequency | 50/60 Hz autoselection |
Frequency Range | 40-70 Hz |
Input Power Factor | 1 |
THDI | ≤3% linear load; ≤5% non-linear load |
Electrical Output | |
Voltages | 1 phase 220/230/240V; 3 phase 380/400/415V |
Voltage THD | ≤1% linear load; ≤3% non-linear load |
Output Receptacles | Hardwired - see manual for terminal block layout |
Overload Capacity | 105% 125% >150%: 0.5s |
Efficiency (Normal Mode) | Up to 96% in Online mode, up to 98.8% in ECO or ESS mode |
Output Frequency | 50/60 Hz autoselect |
Load Crest Factor | ≥3:1 |
Battery | |
Runtime (Minutes) Load (Watts) Battery runtimes are approximate and may vary with equipment, configuration, battery age, temperature, etc. Actual runtime may vary from +/- 15% around these typical values Show: Hover over graph for detailed runtime values | |
Battery Management | ABM® and Temperature compensated charging method (user selectable), automatic battery test, deep discharge protection, automatic recognition of external battery units. |
Extended Battery Capability | EBM |
Communications | |
User Interface | Touchscreen color LCD (with gravity sensor) |
Communication Ports | RS232 DB9; USB 2.0 type-B; programmable dry in/out; Intelligent slot |
Communication Slot | 1 slot for Network-M2 or INDGW-M2 card. |
Environmental & Standards | |
Audible Noise | ≤55dB |
Operating Temperature | 0°C ~ 50 °C (0~40 no derating,40°C~ 50°C derating to 50%) |
Safety markings | CE/TLC/RCM |