Mv-90, Copper Tape Shield Power Cable, 25 Kv, 3/C, Cu/XLPE/Cts/PVC (ICEA S-93-639/NEMA WC71/UL 1072 )

China Mv-90, Copper Tape Shield Power Cable, 25 Kv, 3/C, Cu/XLPE/Cts/PVC (ICEA S-93-639/NEMA WC71/UL 1072), Find details about China Power Cable, XLPE Cable from Mv-90, Copper Tape Shield Power Cable, 25 Kv, 3/C, Cu/XLPE/Cts/PVC (ICEA S-93-639/NEMA WC71/UL 1072)

Model NO.
MV-90
Wire Core Material
Bare Copper Wire
Certification
ISO, CCC
Model
Mv-90
Brand
Boan
Manufacture Standard
Icea S-93-639/NEMA Wc71/UL 1072
Rated Voltage
25 Kv
Number of Cores
3
Section
1 AWG-750 Mcm
Class of Conductor
B
Type of Shield
Copper Tape
Trademark
DingAn
Specification
SGS
Origin
Jiangsu Yixing, China
HS Code
8544601200
Model NO.
MV-90
Wire Core Material
Bare Copper Wire
Certification
ISO, CCC
Model
Mv-90
Brand
Boan
Manufacture Standard
Icea S-93-639/NEMA Wc71/UL 1072
Rated Voltage
25 Kv
Number of Cores
3
Section
1 AWG-750 Mcm
Class of Conductor
B
Type of Shield
Copper Tape
Trademark
DingAn
Specification
SGS
Origin
Jiangsu Yixing, China
HS Code
8544601200
MV-90, Copper Tape Shield Power Cable, 25 KV, 3/C, CU/XLPE/CTS/PVC (ICEA S-93-639/NEMA WC71/UL 1072)
Features

UL Listed as MV-90. Rated as Sunlight Resistance for CT use, 1/0 AWG and larger. Oil Resistance I jacket. True Triple extrusion system and closed handling raw materials system, to eliminate any contact with ambient, until extrusion process ends.

Application
Primary power and distribution circuits in industrial and commercial installations, power circuits in generating plants where line to ground fault current are within shield capabilities. May be used in wet or dry locations, installed in raceways, duct, and open air, aerially or directly buried where permitted by NEC.

Standards
UL 1072: Medium Voltage Power Cables.
ICEA S-93-639/NEMA WC74: 5 kV - 46 kV Shielded Power Cables.
ICEA S-97-682: Standard for Utility Shielded Power Cables Rated 5 kV- 46 kV.
AEIC CS8: Specification for Extruded Dielectric, Shielded Power Cables Rated 5 kV - 46 kV.

Specifications
Maximum operating voltage: 5 kV to 35 kV 100% and 133% IL
Maximum conductor operation temperatures:
Wet and dry locations: Normal: 90 °C, Emergency: 130 °C, Short Circuit: 250 °C

Engineering Information
1. Conductor: Soft annealed uncoated copper compacted Class B per ASTM B496 or hard drawn Aluminum-1350 compacted Class B per ASTM B400.
2. Conductor Shield: Semi conducting cross-linked polyethylene (XLPE).
3. Insulation: Thermoset crosslinked polyethylene (XLPE).
4. Insulation Shield: Semi conducting cross-linked polyethylene (XLPE).
5. Metallic Shield: Soft annealed uncoated copper tape, 5 mil thick, 25% minimum overlap.
6. Assembly: Conductors cabled with non-hygroscopic fillers, as required and binder tape.
7. Jacket: Black sunlight resistance and flame retardant thermoplastic polyvinyl chloride (PVC) compound.

100% Insulation Levels (260 mil)133% Insulation Levels (320 mil)
SizeNumber of StrandsConductor NominalJacket ThicknessApproximate Outside DiameterApproximate Net WeightJacket ThicknessApproximate Outside DiameterApproximate Net Weight
CopperAluminumCopperAluminum
AWG of kcmil
inmilinlb/kftmilinlb/kft
1190.31102.3327662210----
1/0190.341102.41307323721102.7335942892
2/0190.381102.5347425901402.8841893306
3/0190.421102.65402629111402.9846743559
4/0190.481402.83476933651403.1052633859
250370.521402.95530336421403.2258154153
300370.571403.06596539741403.3364924500
350370.621403.16658842621403.4271294803
400370.661403.25719645411403.5277515095
500370.741403.41843851181403.6890175696
600610.811403.6961756301403.94104056418
750610.911403.881157766001404.15122247246