China Hmcxz 108kVA 108kv Hv Hipot Cable Variable Frequency AC Series Resonance Test System, Find details about China AC Resonance Test System, Hv Hipot Cable Variable Frequency from Hmcxz 108kVA 108kv Hv Hipot Cable Variable Frequency AC Series Resonance Test System
Configuration DUT | Reactor 27kVA/27kV 4units | Transformer output | |
35kV/240mm2 Cable(Test voltage:52KV) | Length 1000m | 2 Reactors in parallel and 2 Reactors in series | 3kV |
10kV/300mm2 calbe (Test voltage:24KV) | Length 2000m | 4 Reactors in parallel | 1.5kV |
10.5KV/20KV Generator(Test voltage:24KV) | 60/130KW | 4 Reactors in parallel | 1.5kV |
10kV/35KV Power transformer (Test voltage:44/95KV) | GIS,Tranformer, Insulators.. | 2 Reactors or 4 Reactors in series | 5KV |
Sr no | Description | Specification | Qty |
1 | Variable frequency power supply CHXB-6KV/380V/220V | - Rated output capacity: 6KW - Power Supply: 220V/380V ± 15% (single phase), 50Hz - Output Voltage: 0 - 400V, adjustable; - Rated Output Current: 0-15A; - Frequency: 30 - 300Hz, 0.1Hz step adjustable - Frequency resolution: 0.1Hz - Frequency stability: ≤ 0.02% | 1 unit |
2 | Excitation Transformer JLB-6KVA/1.5KV/5KV/0.2KV/0.4KV | - Rated capacity: 6KVA; - Input voltage: 400V/200V, single phase; - Output voltage :1.5kv/3KV/5kV; - Output current :4A/2A/1.2A; - Frequency:30-300Hz; | 1 unit |
3 | Reactor DK-27KVA/27KV | - Rated Capacity: 27kVA; - Rated voltage: 27kV; - Rated current: 1A; - Induction:110H/each one - Continous wroking time: 60mins; - Temperature rising: <60ºC - Working frequency: :30-300Hz. | 4 units |
4 | Capacitive Divider FRC-120KV/1000PF | - Rated voltage: 120KV - High-voltage capacitance: 1000pF - Frequency:30-300Hz | 1 unit |