China 2088 Shell Universal Air Wind Protective Pressure Sensor, Find details about China Pressure Transducer, Pressure Transmitter from 2088 Shell Universal Air Wind Protective Pressure Sensor
Measuring Medium | Liquid, Gas or Steam |
Pressure Range | -100kPa...0~1kPa...100MPa |
Overload | 1.5 times the full scale |
Pressure Type | Gauge, Absolute or Sealed Gauge |
Accuracy | ±0.25%FS(Representative); ±0.5%FS(Maximum) |
Long-term Stability | ±0.1%FS/year(Representative); ±0.2%FS/year(Maximum) |
Temperature Coefficient of Zero | ±0.03%FS/ºC(Reference 25ºC) |
Temperature Coefficient of Full Scale | ±0.03%FS/ºC(Reference 25ºC) |
Working Temp | -30~85ºC |
Storage Temp | -40~120ºC |
Supply Voltage | 24VDC(12~30V) |
Output Signal | 4~20mADC or Customization |
Output Mode | Two-wire, Three-tire |
Load Resistance | ≤(U-12)/0.02Ω |
Insulation Resistance | 100MΩ, 500VDC |
Protection of Shell | IP65 |
Electrical Connection | Dedicated Shield Cable 1.5 meters |
Housing Material | 304, 316L |
Item NO. | Type | |||||||
HPM280 | Protective Pressure Transmitter | |||||||
Pressure Range | Measuring Range | |||||||
(0~X)kPa | Fill out X directly | |||||||
Code | Output Signal | |||||||
B1 | (4~20)mA | |||||||
B2 | (0~10)mA | |||||||
B3 | (0~10)V | |||||||
B4 | (0~5)V | |||||||
B5 | (1~5)V | |||||||
B6 | (0.5~4.5)V | |||||||
Code | Thread Spec | |||||||
P1 | M20×1.5 | |||||||
P4 | G1/2 | |||||||
P17 | M27×2 | |||||||
Code | Electrical Connection | |||||||
C2 | Cable Outlet | |||||||
Code | Structure&Material | |||||||
Diaphragm | Interface | Shell | ||||||
M1 | 316L | 316L | Stainless Steel | |||||
M2 | 316L | 316L | 316L | |||||
M3 | Tantalum | Hastelloy | 316L | |||||
M4 | Titanium | Titanium | 316L | |||||
X | Other | |||||||
Code | Additional Functions | |||||||
G | Gauge Pressure(Default) | |||||||
A | Absolute Pressure | |||||||
S | Sealed Gauge Pressure | |||||||
v | Fluororubber O-Ring(Default) | |||||||
j | Buna-n O-Ring | |||||||
h | All-welded without O-Ring | |||||||
d | Explosion-proof tYPE, Exd II CT6 | |||||||
D1 | LED Display | |||||||
D2 | LCD Display | |||||||
L | atmospheric pressure measurement within 10kPa | |||||||
W | water-proof and ventilated treatment | |||||||
HPM280 | (0~600)kPa | B1 | P1 | C2 | M1 | GvW |