BS 476-6 Fire Propagation Index Tester

China BS 476-6 Fire Propagation Index Tester, Find details about China Fire Propagation Index Tester, BS 476-6 from BS 476-6 Fire Propagation Index Tester

Model NO.
GD476
Pressure
1kpa
Apparatus Dimensions
400mm (W) X 600mm X (H) X 300mm (D)
Control Module
400mm (W) X 500mm X (H) X 400mm (D)
Weight
About 50kg
Trademark
GOLD
Transport Package
Standard Wooden Case
Origin
Chongqing China(Mainland)
HS Code
9031809090
Model NO.
GD476
Pressure
1kpa
Apparatus Dimensions
400mm (W) X 600mm X (H) X 300mm (D)
Control Module
400mm (W) X 500mm X (H) X 400mm (D)
Weight
About 50kg
Trademark
GOLD
Transport Package
Standard Wooden Case
Origin
Chongqing China(Mainland)
HS Code
9031809090

BS 476-6 Fire Propagation Index Tester

BS 476-6 Fire Propagation Index Tester


Introduction: 

BS 476 part 6 specifies a method of test, the result is expressed as a fire propagation index, that provides a comparative measure of the contribution to the growth of fire made by an essentially flat material, composite or assembly. It is primarily intended for the assessment of the performance of an internal wall and ceiling linings.

Application:

* Building Materials

* Rail

Standard:

BS 476-6---Fire test to Building Material - Fire Propagation

Feature: 

1, Stainless steel support frame and Calcium silicate board combustion chamber.

2, Three kinds of sample holders for different thickness of the specimens.

3, Low reflective black finished mild steel Chimney and Cowl assembly complete with thermocouple mounting points.

4, Compliant stainless steel gas burner.

5, Two K type mineral insulated thermocouples complete with ceramic insulators.

6, Two pencil-type heaters with 1000w installed in the combustion chamber.

7, Control gas instrumentation including electronic gas on/off valve, flow regulating valve, flow meter and manometer.

8, Intelligent single-phase power controller with a feedback loop for accurate control of electric heating elements

9, DAQ record automatically the mV output from the thermocouples of the flue gases throughout the duration of the test.

10, According to the test time, automatically adjust the output power.

Data Acquisition system:

1.  Prompted software interface

2.  Data recording and display of cowl temperature against time

3.  Data recording and display of ambient temperature against time

4.  Display of power value in kW

5.  Calibration routine

6.  Calculation of output rise and calibration value

Specification: 

1)  Electrical: 230 volts Nominal 10 Amps

2)  Ambient Temperature: Operating 10°C to 35°C

3)  Gas Supplies: The gas supply specified in the Standard is Standard test gas G112, as specified in BS 4947.

4)  Flow: Gas flow for burner adjustable from 0 to 5 nl/min.

5)  Pressure: 1kPa

6)  Dimensions: Apparatus: 400mm (W) x 600mm x (H) x 300mm (D)

7)  Control module: 400mm (W) x 500mm x (H) x 400mm (D)

8)  Weight: about 50kg