AC Digital Panel Ammeter

China AC Digital Panel Ammeter, Find details about China Digital Ammeter, Ammeter from AC Digital Panel Ammeter

Model NO.
PM1I, PM1U, CD194I-1x1, CD194U-5X1
Application
Electric Power
Display Ammeter Type
Single-phase Digital
Customized
Customized
Input
1A,5A,
Output
4-20mA
Export Markets
Global
Production Process
Integration
Delivery Time
Depend on Quantity
Trademark
jinhan
Transport Package
Independent Carton Package
Specification
ISO9001
Origin
Zhejiang China
HS Code
9030849000
Model NO.
PM1I, PM1U, CD194I-1x1, CD194U-5X1
Application
Electric Power
Display Ammeter Type
Single-phase Digital
Customized
Customized
Input
1A,5A,
Output
4-20mA
Export Markets
Global
Production Process
Integration
Delivery Time
Depend on Quantity
Trademark
jinhan
Transport Package
Independent Carton Package
Specification
ISO9001
Origin
Zhejiang China
HS Code
9030849000
                                      Digital Panel Meter


Feature
•  Digital inputs,relay outputs and analog output can be option specified
•  Modbus-RTU protocol
•  User programmable,multiple parameters
•  High IP
•  Wide rang of operating temperature
•  Varied formats of panel size


General
PM series digital display AC ammeter can be used to measure distribution system's single or three-phase current. The ammeter's transformer ratio can be programmed. It supports switch volume input, electric relay output, analog output and communication functions (Modbus-RTU Communication Protocol). There are also different installation sizes. It can replace analog pointer ammeters.

Technical Specifications:
AC Digital Panel Ammeter

Shape and installation size:
AC Digital Panel Ammeter


Order form
AC Digital Panel Ammeter
1  Panel size:A2*A1
1:160*160;  2:120*120;  4:120*60;  5:96*48;  6:80*80;  7:72*72;  9:96*96;  D:48*48;
2  Functional code:
I:1 Phase AC TRMS Current;    I3:  3 Phase AC RMS Current;
U:1 Phase AC RMS Voltage;       U3:  3 Phase AC RMS Voltage
W:1 Phase AC Active Power(Watt);   W3: 3 phase Active Power(Watt)
R3: 3 phase Reactive Power(var);      F:Power Frequency;
C:1 & 3 Phase Power Factor
3  Auxillary Power Supply
   A:DC24V;  B:AC/DC85-265V;
4  RS485
   1:have;  2:no
5  Output ranges
A: 0 ... 20 mA into 0-500Ω;  B:4 ... 20 mA into 0-500Ω;  C:4 ...12 ... 20 mA into 0-500Ω;
D: 0 ... 5V, min 1kΩ;   E:1 ... 3 ... 5V, min 1kΩ;   F:1 ... 5V, min 1kΩ; (other ranges on request)
6:  High & low alarm contact
1:have;  2:no
7:   Voltage Input
   A:57.7V;  B:100V;  C:220V; D:380V; (±25% Burden:0.2VA,The PT variable ratio can be set)
8:  Current Input

1:1A,  5:5A;  (Burden:0.3VA typically Permissible overload:2 x rated cotinuous,10 x rated - 10 secs,25 x rated - 2 secs,Frequency:50 or 60 Hz, + 2Hz,The CT variable ratio can be set)

1 Phase AC TRMS Current:
Panel SizeModelsRS4854-20mAalarm contact
160*80PM1I111
120*120PM2I111
80*80PM6I111
120*60PM4I111
96*48PM5I111
96*96PM9I111
72*72PM7I111
48*48PMDI1--
("1" : indicating this feature, "-" means not having this function)

3 Phase AC RMS Current
Panel SizeModelsRS4854-20mAalarm contact
160*80PM1I111
120*120PM2I111
80*80PM6I111
120*60PM4I111
96*48-111
96*96PM9I111
72*72PM7I111
48*48----