Approvals:TÜV EN50618 H1Z2Z2-K
Product features:1.Rated Voltage: DC 1500V
2.Ambient Temperature: -40ºC--90ºC Max. Temperature at Conductor 120ºC:
3.Conductor: Tin-Plated copper, Class5
4.Insulation: 125ºC XLPE
5.Jacket: 125ºC XLPE
6.Color: Black
7.Marking: FRCABLE TÜV EN50618 H1Z2Z2-K DC 1.5KV, 1X4.0mm2 Meter marking
Application: For the cabling between the solar moudules and as extension cable between the moudle strings and the DC/AC inverter. Photovoltaic plants and solar parks. Gable and flat roof PV systems.
Cable Technical Data:Conductor | Insulation | Jacket |
Guage | No. | OD. | Avg.Thickness | Avg.Thickness |
mm2 | N/mm | mm | mm | mm |
1*6 | 84/0.285 | 3.05 | 0.90 | 0.80 |
item | Unit | Values |
Conductor Res(20ºC) | Ω/km | ≤3.39 |
Insulation Res (90ºC) | Ω·cm | ≥109 |
Withstand voltage | V/5min | AC6500 |
Connector Technical Data:Electrical Features: |
Rated Current | 22A(2.5mm2), 35A(4mm2), 40A(6mm2) |
Withstanding Voltage | 1000V DC |
Contact Resistance | ≤0.3mΩ |
Protection Class | Class II |
Mechanical Features: |
Temperature Range | -40 ºC~+90ºC |
Protection Degree | IP67 |
Wire Size Range | 2.5/4/6 mm2(14AWG,12AWG,10AWG) |
Unmating Force | 200 Newton |
Material Features: |
Insulation Material | PC |
Contact Material | Copper,Tin plated |
Flame Class | UL94-V0 or UL94-5VA |