Meaning | Value range | Unit | Remark |
Communication mode | RS485/RS232 | - | Type of port communicating with the background. Default =RS485 |
Device number | 0-247 | - | Unique confirmation number addressed on the background, the terminals in same network can not have same number. Default=1 |
Communication rate | 1200-115200 | bps | Rate of communication with background, which is same as it of the background. Default=9600 |
System password | 0-9999 | - | Password for entering parameter setup |
Background light delay | 0-360 | s | Duration after which the system will automatically turn off the screen in case of normal system operation (no alarms) and no user key operation. 0 indicates that the screen will keep on. Default=180 |
Control strategy | Voltage reactive/power factor | - | Adopted switching mode. Default=reactive voltage |
I-section current change | 1-9999 | - | I busbar current mutual inductor change ratio, E.g.
Default=40 |
I-section voltage radio | 60-900 | - | Voltage transformer ratio of I-section busbar. Default=100 |
I-section switch-on delay | 0.1-3000.0 | s | Delay of capacitor switch-on of I-section busbar. E.g. if it is set as 10.0, the delay is 10 (10.0×1s). The default is 20.0 |
I-section release delay | 0.1-3000.0 | s | Delay of capacitor release of I-section busbar. E.g. if it is set as 10.0. the delay is 10s (10.0×1s). The default is 10.0 |
I-section switch-on interval | 0.1-3000.0 | s | Interval after which the capacitor switches on after the I-section busbar capacitor is released, namely discharging time of capacitor. E.g. if it is set as 10.0, the interval is 10s (10.0x1s). the default is 600.0 |
I-section alarm release delay | 0-3000.0 | s | Delay for releasing capacitors in turn after the I-section busbar detects the system alarm signals. When it is set as 0, it indicates to release all once. The default is 1.0 |
I-section over-voltage threshold | 0-90.00 | kV | I-section busbar over-voltage alarm point. When the system voltage is higher than this value, give out an alarm and release all switch-on capacitors till the alarm is released. 0 indicates disabled. Default=0 Notice: disabled indicates no over-voltage alarm. |
I-section over-voltage delay | 0-3000.0 | s | When I-section busbar detects the over-voltage alarm signal in which the duration is over this value, give out an alarm. When the duration is less than this value, ignore this alarm signal. 0 indicates real-time alarm. The default is 0 |
I-section under-voltage threshold | 0-90.00 | kV | I-section busbar under-voltage alarm point. When the system voltage is less than this value, give out an alarm and release all switch-on capacitors till the alarm is released. 0 indicates disabled. The default is 8.00 Notice: disabled indicates no under-voltage alarm. |
I-section under-voltage delay | 0-3000.0 | s | When I-section busbar detects the under-voltage alarm signal in which the duration is over this value, give out an alarm. When the duration is less than this value, ignore this alarm signal. 0 indicates real-time alarm. The default is 0 |
I-section voltage harmonic wave over-limit | 0-100 | % | Over-limit alarm value of total distortion rate of I-section busbar voltage harmonic wave, when the system harmonic wave is over this value, give out an alarm and release all switch-on capacitor till the alarm is released. 0 indicates disabled. The default is 0 Notice: disabled indicates no voltage harmonic wave alarm. |
I-section voltage harmonic wave delay | 0-3000.0 | s | When I-section busbar detects the harmonic wave over-limit alarm signal in which the duration is over this value, give out an alarm. When the duration is less than this value, ignore this alarm signal. 0 indicates real-time alarm. The default is 0 |
I-section power factor over-limit | 0.85L-0.85C | - | Ceiling and floor limit target of power factor of I-section busbar compensation, finally the power factor is compensated to reach a value between the ceiling limit and floor limit of the target power factor. The floor limit setting can not be over the ceiling limit. If the ceiling limit is same as the floor limit, it indicates one target power factor. The unit L indicates inductance and C indicates tolerance. The tolerance is more than inductance value. The default is 1.00 Notice: the control strategy is valid in case of power factor mode. |
Floor ceiling of I-section power factor | - | ||
I-section return differential voltage | 0-1.00 | kV | Over-voltage and under-voltage return differential value of I-section busbar, after over-voltage, when the system voltage is less than over-voltage threshold-return differential voltage, the over-voltage alarm can be released. After unver-voltage, when the system voltage is over the under-voltage threshold plus return differential voltage, the under-voltage alarm can be released. The default is 0. |
Ceiling limit of I-section reactive power | (-10000)-(10000) | kVar | Ceiling and floor limit target of reactive power of I-section busbar compensation, finally the reactive power is compensated to reach a value between the ceiling limit and floor limit of the reactive power. The floor limit setting of reactive power can not be over the ceiling limit. If the ceiling limit is same as the floor limit, it indicates one target reactive power. The "-" indicates tolerance. The tolerance is less than inductance value. The default is 0 Notice: the control strategy is valid in case of voltage reactive power mode. |
Floor limit of I-section reactive power | kVar | ||
I-section voltage switch-on threshold | 0-90.00 | kV | Voltage ceiling limit and floor limit target of I-section busbar compensation, finally the voltage will be compensated to reach a value between the voltage switch-on threshold and voltage release threshold. The voltage switch-on threshold setting can not be more than voltage release threshold. The default switch-on voltage threshold is 9.00. the release voltage threshold is 11.00 Notice: the control strategy is valid in case of voltage reactive power mode |
I-section voltage release threshold | kV | ||
I-section switching influence voltage | 0-1.00 | kV | Maximum voltage change due to one switch-on capacitor in I-section busbar, the voltage reactive power switching scheme gives the protection value of switch-on voltage and release voltage. The default is 0.01 |
II-section current change | 1-9999 | - | II busbar current mutual inductor change ratio, E.g.
Default=40 |
II-section voltage radio | 60-990 | - | Voltage transformer ratio of II-section busbar. Default=100 |
II-section switch-on delay | 0.1-3000.0 | s | Delay of capacitor switch-on of II-section busbar. E.g. if it is set as 10.0, the delay is 10 (10.0×1s). The default is 20.0 |
II-section release delay | 0.1-3000.0 | s | Delay of capacitor release of II-section busbar. E.g. if it is set as 10.0. The delay is 10s (10.0×1s). The default is 10.0 |
II-section switch-on interval | 0.1-3000.0 | s | Interval after which the capacitor switches on after the II-section busbar capacitor is released, namely discharging time of capacitor. E.g. if it is set as 10.0, the interval is 10s (10.0x1s). the default is 600.0 |
II-section alarm release delay | 0-3000.0 | s | Delay for releasing capacitors in turn after the II-section busbar detects the system alarm signals. When it is set as 0, it indicates to release all once. The default is 1.0 |
II-section over-voltage threshold | 0-90.00 | kV | II-section busbar over-voltage alarm point. When the system voltage is higher than this value, give out an alarm and release all switch-on capacitors till the alarm is released. 0 indicates disabled. Default=0 Notice: disabled indicates no over-voltage alarm. |
II-section over-voltage delay | 0-3000.0 | s | When II-section busbar detects the over-voltage alarm signal in which the duration is over this value, give out an alarm. When the duration is less than this value, ignore this alarm signal. 0 indicates real-time alarm. The default is 0 |
II-section under-voltage threshold | 0-90.00 | kV | II-section busbar under-voltage alarm point. When the system voltage is less than this value, give out an alarm and release all switch-on capacitors till the alarm is released. 0 indicates disabled. The default is 8.00 Notice: disabled indicates no under-voltage alarm. |
II-section under-voltage delay | 0-3000.0 | s | When II-section busbar detects the under-voltage alarm signal in which the duration is over this value, give out an alarm. When the duration is less than this value, ignore this alarm signal. 0 indicates real-time alarm. The default is 0 |
II-section voltage harmonic wave over-limit | 0-100 | % | Over-limit alarm value of total distortion rate of II-section busbar voltage harmonic wave, when the system harmonic wave is over this value, give out an alarm and release all switch-on capacitor till the alarm is released. 0 indicates disabled. The default is 0 Notice: disabled indicates no voltage harmonic wave alarm |
II-section voltage harmonic wave delay | 0-3000.0 | s | When II-section busbar detects the harmonic wave over-limit alarm signal in which the duration is over this value, give out an alarm. When the duration is less than this value, ignore this alarm signal. 0 indicates real-time alarm. The default is 0 |
II-section power factor over-limit | 0.85L-0.85C | - | Ceiling and floor limit target of power factor of I-section busbar compensation, finally the power factor is compensated to reach a value between the ceiling limit and floor limit of the target power factor. The floor limit setting can not be over the ceiling limit. If the ceiling limit is same as the floor limit, it indicates one target power factor. The unit L indicates inductance and C indicates tolerance. The tolerance is more than inductance value. The default is 1.00 Notice: the control strategy is valid in case of power factor mode. |
Floor ceiling of II-section power factor | - | ||
II-section return differential voltage | 0-1.00 | kV | Over-voltage and under-voltage return differential value of II-section busbar, after over-voltage, when the system voltage is less than over-voltage threshold-return differential voltage, the over-voltage alarm can be released. After unver-voltage, when the system voltage is over the under-voltage threshold plus return differential voltage, the under-voltage alarm can be released. The default is 0. |
Ceiling limit of II-section reactive power | (-10000)-(10000) | kVar | Ceiling and floor limit target of reactive power of II-section busbar compensation, finally the reactive power is compensated to reach a value between the ceiling limit and floor limit of the reactive power. The floor limit setting of reactive power can not be over the ceiling limit. If the ceiling limit is same as the floor limit, it indicates one target reactive power. The "-" indicates tolerance. The tolerance is less than inductance value. The default is 0 Notice: the control strategy is valid in case of voltage reactive power mode. |
Floor limit of II-section reactive power | kVar | ||
II-section voltage switch-on threshold | 0-90.00 | kV | Voltage ceiling limit and floor limit target of II-section busbar compensation, finally the voltage will be compensated to reach a value between the voltage switch-on threshold and voltage release threshold. The voltage switch-on threshold setting can not be more than voltage release threshold. The default switch-on voltage threshold is 9.00. the release voltage threshold is 11.00 Notice: the control strategy is valid in case of voltage reactive power mode |
II-section voltage release threshold | kV | ||
II-section switching influence voltage | 0-1.00 | kV | Maximum voltage change due to one switch-on capacitor in II-section busbar, the voltage reactive power switching scheme gives the protection value of switch-on voltage and release voltage. The default is 0.01 |
Power on operation delay | 15-3600 | s | Switching operation delay after the controller starts. The default is 180 |
Switch position signal detection | Disabled/enabled | - | Position signal detection for enabling or disabling external switching switch. The default is disabled |
Ceiling limit of daily switch-on time | 0-10000 | time | Ceiling limit of daily switch-on capacitor time, after this limit, the output will be locked till wee hours on next day. The time will be reset to zero. 0 indicates disabled. The default is 0 Notice: disabled indicates no time protection function. |
Channel 01 capacitance | 0-10000 | kVar | Capacitance of channel 1 capacitor, this value is the actual switch-on capacitance Notice: 0 indicates no capacitance in this channel |
Channel 02 capacitance | 0-10000 | kVar | Capacitance of channel 2 capacitor, this value is the actual switch-on capacitance Notice: 0 indicates no capacitance in this channel |
Channel 03 capacitance | 0-10000 | kVar | Capacitance of channel 3 capacitor, this value is the actual switch-on capacitance Notice: 0 indicates no capacitance in this channel |
Channel 04 capacitance | 0-10000 | kVar | Capacitance of channel 4 capacitor, this value is the actual switch-on capacitance Notice: 0 indicates no capacitance in this channel |
Channel 05 capacitance | 0-10000 | kVar | Capacitance of channel 5 capacitor, this value is the actual switch-on capacitance Notice: 0 indicates no capacitance in this channel |
Channel 06 capacitance | 0-10000 | kVar | Capacitance of channel 6 capacitor, this value is the actual switch-on capacitance Notice: 0 indicates no capacitance in this channel |
Channel 07 capacitance | 0-10000 | kVar | Capacitance of channel 7 capacitor, this value is the actual switch-on capacitance Notice: 0 indicates no capacitance in this channel |
Channel 08 capacitance | 0-10000 | kVar | Capacitance of channel 8 capacitor, this value is the actual switch-on capacitance Notice: 0 indicates no capacitance in this channel |