1000va, 2000va , 3000va Industrial Inverter

China 1000va, 2000va, 3000va Industrial Inverter, Find details about China Industrial Inverter, 3000va from 1000va, 2000va, 3000va Industrial Inverter

Port: Shenzhen, China
Transport Package: Carton
Payment Terms: L/C, T/T
Trademark: Goldpower
Origin: China
 
 
  






GPDA1000VA-A
Input:40-60Vdc;  Output :220Vac; Capacity:1000VA








 
    
   
 
  


















 





ISO9001-2000 Certified
Professional Power Supply Manufacturer
Shenzhen Goldpower Tech Co., LTD

Address: 1301 Bldg A, New-tech Plaza Tian'an Cyber Park, Futian District,     Shenzhen City.
Tel: +86 755-83432128  83433146   Fax: +86 755-83432651 83437956
Website: http://szgoldpower.en.made-in-china.com   Postal code: 518040

Preface



 Welcome to use GPDA1000VA-A,GPDA1000VA-A from Gold Power, consisting of two outputs, bypass AC input, with RS485 com port. Due to the latest circuit design, it is compact and of reliable performance, and the system is equipped with protections against input reversed polarity, over temperature, output short-circuit, over-current and over-voltage. The power supply is designed strictly in accordance with the safety regulations, which conforms to the safety standards and requirements of information technology.
Statement
  1. The performance of GPELU4806-10 embedded power system is detailed in the specification. Please learn the specification before any operation is conducted in compliance with safety rules. Our warrant will not apply to any damage of product caused by improper operation or utilization out of range specified in this specification.
  2. The information in this specification is subject to change without any notice.
Safety rules
 
 
High voltage!
AC input line is high voltage operating line. Be sure that the AC input is cut off before implementing any operations. Warning signs shall be tagged to the switches that should not be touched during operating process.
 
Caution! AC terminals and other unnecessarily bare part shall be strictly insulated.
 
Caution!The device shall be securely grounded before power-on.
Caution!The module is hot-swappable; please make sure that all indicators on module panel is under state of off before the module is inserted.
 
 Any operation at AC & high voltage under lightning is forbidden.


1. Parameters


 
Input
ParameterMin.TypMax.UnitRemarks
DC inputWorking voltage range40 60Vdc 
Rated voltage 48 Vdc 
Rated current  30ARated input, Rated output.
Max surge current  45A rated 150%
AC outputWorking voltage range200 240Vac 
Rated voltage 220 Vac 
Rated current  5A 
 
Output
ParameterMin.TypMax.UnitRemarks
Inverter Output Rated voltage 220 VacFull input range
Rated current 4.6 A 
Voltage accuracy  ±5%Full input range
Rated Frequency 495051Hz 
Rated capacity  1000VA 
Rated power  1000W 
Efficiency85  %Rated working condition
Power factor0.8   Rated working condition
Dynamic transient recovery time  60ms 
WaveformSine wave THD<3%(linear load)
Sine waveTHD<8%(non-linear load)
Overload capacity105~125% load for more than10 mins, 125~150%load for more than10 secs.
Output current peak ratio3:1
Output QTYTwo AC outputs
Bypass AC output Output voltage range200 240VacChanges according to AC voltage's changing.
Rated voltage 220 Vac 
Rated current  5A 
 Inverter switches to grid's time.   20msRated load
Grid switches to inverter's time.   100msRated load
Output descriptionShare the same output terminals to the inverter. When there is AC input, use the grid. When AC fail, automatically switch to the inverter and then power the equipments.
        


1. Parameters
 
Protections
ParameterMin.TypicalMax.UnitRemarks
Inverter DC input UVP set point36  Vdc 
DC input UVP recovery point  40VdcRecover in 1 min
DC input UVP tolerance2  Vdc 
DC input OVP set point  66Vdc 
DC input OVP recovery point60  VdcRecover in 1 min
DC input OVP tolerance2  Vdc 
OCPOCP without auto-recovery function.
OTPCut off power when the heat sinking is over temperature.
Anti-reverse connectionInverter will not work when reverse connecting the input.
Short protectionWhen inverter shorts, it'll auto restart every 1 min, if the inverter become normal, it can auto-recover. If it short for long time, the inverter will stop working.
Output OCPWhen inverter is over current, it'll auto restart every 1 min, if the inverter become normal, it can auto-recover. If it is over current for long time, the inverter will stop working.
 AlarmWhen there is input abnormal, overload, short, inverter malfunction, can hear the buzzer.
Bypass input Input OCP Can't auto-recover.
 
Ambient requirements
ParametersMinTyp.MaxUnitRemark
Operating temp-20 +55°C 
Storage temp-25 +70°C 
Humidity0 95%Relative humidity, no condensing
Altitude  1500mComplied with GB3859.2-93
CoolingNatural cooling
 
Insulation rating
ParameterRequirementRemark
Insulating strengthInput - output:1500Vac/10mA//1minNo flashover or breakdown
 
Input -earth:1500Vac/10mA//1min
Output-earth:500Vac/10mA//1min
Insulation resistance@ normal atmospheric pressure, relative humidity: 90%  Testing voltage: 500v dc  The insulation resistance of input-output, input-ground, output-ground shall not be less than 10MΩ
 
EMC
Conducted emissionComplied with YD/T983-1998 class A
Radiated emissionComplied with YD/T983-1998 class A
 Immunity Complied with YD/T983-1998  class A
Reverse irrigation broadband noise current relative value<10%
Noise<50dB(1m)
Dedust Functional
SmellNo harmful gas
1. Parameters

 
Mechanical specifications
L*W*H (mm)Refer to following chart
Weight(kg)4kg
\* MERGEFORMAT
























































2. Signals


2.1,LED definition
 
Alarms
No.StatusLED indicator  Remark
1Green flicker  NormalReport input voltage, current, temperature through 485 port, together with  input OVP,UVP, OCP, OTP, fan fail,, etc.
Red off
Purple off
2Green onInput UVP, OVP, short, overload, OTP, protection. Fan fail
Red flicker
Purple off
3 Green off Malfunction
Red flicker
Purple off
4 Green off Input reverse connection, inverter malfunction.
Red off
Purple off
5 Green on AC grid normal.
Red off
Purple on



2.2 Terminals' definition

\* MERGEFORMAT































3. Installation

\* MERGEFORMAT 3.1 Embedded



















Dimension

Installation method:
Insert the inverter into the specific position, in order to guarantee it's positioned properly, the hungers should be screwed with 4 of M6 screws.

\* MERGEFORMAT 3.2 wall-mounted type











Dimension
Installation method:
As shown on above drawing, you need to fill in the wall with 4 of M6 setscrews, and then fix the inverter on to the wall.