China 1000va, 2000va, 3000va Industrial Inverter, Find details about China Industrial Inverter, 3000va from 1000va, 2000va, 3000va Industrial Inverter
Port: | Shenzhen, China
|
---|---|
Transport Package: | Carton |
Payment Terms: | L/C, T/T |
Trademark: | Goldpower |
---|---|
Origin: | China |
ISO9001-2000 Certified Professional Power Supply Manufacturer | Shenzhen Goldpower Tech Co., LTD Address: 1301 Bldg A, New-tech Plaza Tian'an Cyber Park, Futian District, Shenzhen City. Tel: +86 755-83432128 83433146 Fax: +86 755-83432651 83437956 Website: http://szgoldpower.en.made-in-china.com Postal code: 518040 |
High voltage! | AC input line is high voltage operating line. Be sure that the AC input is cut off before implementing any operations. Warning signs shall be tagged to the switches that should not be touched during operating process. |
Caution! | AC terminals and other unnecessarily bare part shall be strictly insulated. |
Caution! | The device shall be securely grounded before power-on. |
Caution! | The module is hot-swappable; please make sure that all indicators on module panel is under state of off before the module is inserted. |
Any operation at AC & high voltage under lightning is forbidden. |
Input | ||||||
Parameter | Min. | Typ | Max. | Unit | Remarks | |
DC input | Working voltage range | 40 | 60 | Vdc | ||
Rated voltage | 48 | Vdc | ||||
Rated current | 30 | A | Rated input, Rated output. | |||
Max surge current | 45 | A | ≤ rated 150% | |||
AC output | Working voltage range | 200 | 240 | Vac | ||
Rated voltage | 220 | Vac | ||||
Rated current | 5 | A |
Output | |||||||
Parameter | Min. | Typ | Max. | Unit | Remarks | ||
Inverter Output | Rated voltage | 220 | Vac | Full input range | |||
Rated current | 4.6 | A | |||||
Voltage accuracy | ±5 | % | Full input range | ||||
Rated Frequency | 49 | 50 | 51 | Hz | |||
Rated capacity | 1000 | VA | |||||
Rated power | 1000 | W | |||||
Efficiency | 85 | % | Rated working condition | ||||
Power factor | 0.8 | Rated working condition | |||||
Dynamic transient recovery time | 60 | ms | |||||
Waveform | Sine wave THD<3%(linear load) | ||||||
Sine waveTHD<8%(non-linear load) | |||||||
Overload capacity | 105~125% load for more than10 mins, 125~150%load for more than10 secs. | ||||||
Output current peak ratio | 3:1 | ||||||
Output QTY | Two AC outputs | ||||||
Bypass AC output | Output voltage range | 200 | 240 | Vac | Changes according to AC voltage's changing. | ||
Rated voltage | 220 | Vac | |||||
Rated current | 5 | A | |||||
Inverter switches to grid's time. | 20 | ms | Rated load | ||||
Grid switches to inverter's time. | 100 | ms | Rated load | ||||
Output description | Share the same output terminals to the inverter. When there is AC input, use the grid. When AC fail, automatically switch to the inverter and then power the equipments. | ||||||
Protections | ||||||
Parameter | Min. | Typical | Max. | Unit | Remarks | |
Inverter | DC input UVP set point | 36 | Vdc | |||
DC input UVP recovery point | 40 | Vdc | Recover in 1 min | |||
DC input UVP tolerance | 2 | Vdc | ||||
DC input OVP set point | 66 | Vdc | ||||
DC input OVP recovery point | 60 | Vdc | Recover in 1 min | |||
DC input OVP tolerance | 2 | Vdc | ||||
OCP | OCP without auto-recovery function. | |||||
OTP | Cut off power when the heat sinking is over temperature. | |||||
Anti-reverse connection | Inverter will not work when reverse connecting the input. | |||||
Short protection | When inverter shorts, it'll auto restart every 1 min, if the inverter become normal, it can auto-recover. If it short for long time, the inverter will stop working. | |||||
Output OCP | When inverter is over current, it'll auto restart every 1 min, if the inverter become normal, it can auto-recover. If it is over current for long time, the inverter will stop working. | |||||
Alarm | When there is input abnormal, overload, short, inverter malfunction, can hear the buzzer. | |||||
Bypass input | Input OCP | Can't auto-recover. |
Ambient requirements | |||||
Parameters | Min | Typ. | Max | Unit | Remark |
Operating temp | -20 | +55 | °C | ||
Storage temp | -25 | +70 | °C | ||
Humidity | 0 | 95 | % | Relative humidity, no condensing | |
Altitude | 1500 | m | Complied with GB3859.2-93 | ||
Cooling | Natural cooling |
Insulation rating | ||
Parameter | Requirement | Remark |
Insulating strength | Input - output:1500Vac/10mA//1min | No flashover or breakdown |
Input -earth:1500Vac/10mA//1min | ||
Output-earth:500Vac/10mA//1min | ||
Insulation resistance | @ normal atmospheric pressure, relative humidity: 90% Testing voltage: 500v dc The insulation resistance of input-output, input-ground, output-ground shall not be less than 10MΩ |
EMC | |
Conducted emission | Complied with YD/T983-1998 class A |
Radiated emission | Complied with YD/T983-1998 class A |
Immunity | Complied with YD/T983-1998 class A |
Reverse irrigation broadband noise current relative value | <10% |
Noise | <50dB(1m) |
Dedust | Functional |
Smell | No harmful gas |
Mechanical specifications | |
L*W*H (mm) | Refer to following chart |
Weight(kg) | ≤4kg |
Alarms | |||
No. | Status | LED indicator | Remark |
1 | Green flicker | Normal | Report input voltage, current, temperature through 485 port, together with input OVP,UVP, OCP, OTP, fan fail,, etc. |
Red off | |||
Purple off | |||
2 | Green on | Input UVP, OVP, short, overload, OTP, protection. Fan fail | |
Red flicker | |||
Purple off | |||
3 | Green off | Malfunction | |
Red flicker | |||
Purple off | |||
4 | Green off | Input reverse connection, inverter malfunction. | |
Red off | |||
Purple off | |||
5 | Green on | AC grid normal. | |
Red off | |||
Purple on |