China Protector/DIN Rail Adjustable Over Under Protective Protector/Relay Protection/Electricity Voltage Protector Over/Under-Voltage Protector Wjgq-36A/4p, Find details about China Voltage Protection Relays, Phase Protection Relay from Protector/DIN Rail Adjustable Over Under Protective Protector/Relay Protection/Electricity Voltage Protector Over/Under-Voltage Protector Wjgq-36A/4p
Data Specs for Auto Reset Over/Under Voltage Protector Device :
1, Application:
communication, television broadcasting, computer room, automatic control, and mechanical equipment, and all distribution equipment lightning protection.
2, Main function:
1, when the single-phase line has over-voltage or under-voltage, the line is cut off, and the single-phase line voltage returns to normal after a delay and automatically resets to connect the line. |
2, when the transient or transient overvoltage occurs on the line, the protector will not malfunction. |
3, when the line fault voltage is the highest, the protector itself will not be damaged. |
4, the protector does not connect to the line when the voltage is unstable due to faults such as false contacts or when the power is suddenly cut off and then the power comes on. |
5, the protector has an inverse time action characteristic, and the action time is ≤1s. |
6, voltage protection range: 0-450V below 40A, 50/60A: 0-600W. |
7, withstand impulse voltage: 4kV(in line with the safety standards of Class III electrical appliances). |
8, the protector has two-color light-emitting diodes to the working status, green: normal voltage indication, red: over-under voltage or delay indication. |
3, Features:
A. Small size but high switching capacity. |
B. Built-in high-performance MCU provides precise voltage protection. |
C. Energy-saving, driven by instantaneous impulse coil. |
D. Cost-effective, improved circuit design consumes very low power. |
E. Flame retardant cover provides good fire, heat, and weather resistance. |
F. Withstand the impact voltage: 5KV. |
G. Outline Modulus Design: Rail mounting. |
4, Main Technical Parameters
Project | Parameter |
Operating Voltage | AC 220V, Frequency: 50Hz |
Product specifications | 20A, 32A, 40A, 50A, 63A (Resistance) |
Load power | 4.4KVA, 6.6KVA, 8.8KVA, 11KVA, 13.2KVA |
Overvoltage action cut-off value | AC 270±5V |
Overvoltage recovery value | AC 255±5V |
Undervoltage action cut-off value | AC 170±5V |
Undervoltage recovery value | AC 185±5V |
Delay after power failure | 30±10 second |
Action delay time | ≤1 s |
Own power consumption | ≤2 W |
Electrical machinery life | ≥10 million times |
Standards compliant | JB/T 12762-2015 <<OUPA>> |
Project | Parameter |
Input method | Lower input, upper output |
Upper input, lower output | |
Installation method | 36mm standard rail installation |
Dimensions | 2P/77*36*65mm( L*W*H) 4P/77*72*65mm (L*W*H) |