Cotrust Cth200 PLC Sm231 High Precision Analog Module Voltage Input, 8 Channels (231-0HF32) PLC

China Cotrust Cth200 PLC Sm231 High Precision Analog Module Voltage Input, 8 Channels (231-0HF32) PLC, Find details about China Cotrust, Digital Input from Cotrust Cth200 PLC Sm231 High Precision Analog Module Voltage Input, 8 Channels (231-0HF32) PLC

Model NO.
CTH2 231-0HF32
Customized
Customized
Weight
0.2kg
Trademark
COTRUST
Transport Package
CTN
Specification
71*80*62mm
Origin
China
HS Code
853710119
Model NO.
CTH2 231-0HF32
Customized
Customized
Weight
0.2kg
Trademark
COTRUST
Transport Package
CTN
Specification
71*80*62mm
Origin
China
HS Code
853710119

Order Data

Model No.DescriptionOrder No.
SM231SM231 High precision analog voltage input,8*16BIT, optocoupling isolationCTH2 231-0HF32

Performance Parameters

Physical Features 

Dimension(W×H×D)

71×80×62mm

LED indicator

24V power indicator, on: power supply is normal, off:  power supply failure

Power loss

+5VDC consumes current

44 mA

L+

31mA

L+ coil voltage range

20.4~28.8V DC

Power loss

2.5 W

Analog Input Features 

Analog input 

8

Isolation (between field and logic circuits)

 

Optical coupling isolation

Input type

Differential input

Scale range

Voltage input (unipolar)

0~10V, 0~5V

Voltage input (bipolar)

±5V,±2.5V

Data word format

Unipolar, full range

0~32000

Bipolar, full range

-32000~32000

Input resolution

Voltage input (unipolar)

300μV (0~10V range))

150μV (0~5V range))

Voltage input (bipolar)

150μV (±5V range))

75μV (±2.5V range))

Conversion time

10ms

Eight channel conversion time

 

100ms

Common mode rejection

40dB,DC - 60Hz

Common mode voltage

Signal Voltage + Common Mode Voltage (must be less than or equal to 12V)

Input impedance

no lessthan 10MΩ

Maximum input voltage

30V

Maximum input current

30mA

AD converter resolution

16bit

Addressing mode

VW addressing

Range selection and software configuration
Cotrust Cth200 PLC Sm231 High Precision Analog Module Voltage Input, 8 Channels (231-0HF32) PLC
[Range selection switch position]

The following table shows how to set the range of the SM231 8AI module with the DIP switch. Switches 1, 2 and 3 can select the analog input range. All inputs are set to the same analog input range. In the following table, ON means connection and OFF means no connection. It is important to note that unused DIP switches SW4 ~ SW6 must be set to the OFF position.

Single polarity

Full scale input

Resolution 

SW1

SW2

SW3

ON

OFF

ON

0-10V

300μV

ON

OFF

0 - 5V

150μV

Bipolar

Full scale input

 Resolution 

SW1

SW2

SW3

OFF

OFF

ON

± 5V

150μV

ON

OFF

± 2.5 V

75μV

 

[Software Configuration]

For the SM231 8AI× 16-bit analog input module, its reading is in VW, not AIW, the relative position of the module is different, the corresponding address is different. The address calculation formula is as follows:

X (VWx) = slot number × 64 + input channel number × 2

The slot number corresponds to the module's installation location, with the first extension slot next to the CPU being 0, the second extension slot being 1, and so on. There are 8 input channels, from A to G, and the corresponding numbers are 0 to 7.

 

VWxx

Channel 0

Channel 1

Channel 2

Channel 3

Channel 4

Channel 5

Channel 6

Channel 7

Slot 0

VW0

VW2

VW4

VW6

VW8

VW10

VW12

VW14

Slot 1

VW64

VW66

VW68

VW70

VW72

VW74

VW76

VW78

Slot 2

VW128

VW130

VW132

VW134

VW136

VW138

VW140

VW142

Slot 3

VW192

VW194

VW196

VW198

VW200

VW202

VW204

VW206

Slot 4

VW256

VW258

VW260

VW262

VW264

VW266

VW268

VW270

Slot 5

VW320

VW322

VW324

VW326

VW328

VW330

VW332

VW334

Slot 6

VW384

VW386

VW388

VW390

VW392

VW394

VW396

VW398


Note:  Because the offset address of TD2X text display is also in VW0, so If you need to use Td2X text display in your system, please don't put the EM231 8AI×TC module in slot 0, or the TD2X will not work normally. Siemens TD200 text displayer is same as TD2X.