China Cotrust Cth200 PLC Sm231 High Precision Analog Module Voltage Input, 8 Channels (231-0HF32) PLC, Find details about China Cotrust, Digital Input from Cotrust Cth200 PLC Sm231 High Precision Analog Module Voltage Input, 8 Channels (231-0HF32) PLC
Order Data
Model No. | Description | Order No. |
SM231 | SM231 High precision analog voltage input,8*16BIT, optocoupling isolation | CTH2 231-0HF32 |
Performance Parameters
Physical Features | |
Dimension(W×H×D) | 71×80×62mm |
LED indicator | 24V power indicator, on: power supply is normal, off: power supply failure |
Power loss | |
+5VDC consumes current | 44 mA |
L+ | 31mA |
L+ coil voltage range | 20.4~28.8V DC |
Power loss | 2.5 W |
Analog Input Features | |
Analog input | 8 |
Isolation (between field and logic circuits)
| Optical coupling isolation |
Input type | Differential input |
Scale range | |
Voltage input (unipolar) | 0~10V, 0~5V |
Voltage input (bipolar) | ±5V,±2.5V |
Data word format | |
Unipolar, full range | 0~32000 |
Bipolar, full range | -32000~32000 |
Input resolution | |
Voltage input (unipolar) | 300μV (0~10V range)) 150μV (0~5V range)) |
Voltage input (bipolar) | 150μV (±5V range)) 75μV (±2.5V range)) |
Conversion time | 10ms |
Eight channel conversion time
| 100ms |
Common mode rejection | 40dB,DC - 60Hz |
Common mode voltage | Signal Voltage + Common Mode Voltage (must be less than or equal to 12V) |
Input impedance | no lessthan 10MΩ |
Maximum input voltage | 30V |
Maximum input current | 30mA |
AD converter resolution | 16bit |
Addressing mode | VW addressing |
Range selection and software configuration
[Range selection switch position]
The following table shows how to set the range of the SM231 8AI module with the DIP switch. Switches 1, 2 and 3 can select the analog input range. All inputs are set to the same analog input range. In the following table, ON means connection and OFF means no connection. It is important to note that unused DIP switches SW4 ~ SW6 must be set to the OFF position.
Single polarity | Full scale input | Resolution | ||
SW1 | SW2 | SW3 | ||
ON | OFF | ON | 0-10V | 300μV |
ON | OFF | 0 - 5V | 150μV | |
Bipolar | Full scale input | Resolution | ||
SW1 | SW2 | SW3 | ||
OFF | OFF | ON | ± 5V | 150μV |
ON | OFF | ± 2.5 V | 75μV |
[Software Configuration]
For the SM231 8AI× 16-bit analog input module, its reading is in VW, not AIW, the relative position of the module is different, the corresponding address is different. The address calculation formula is as follows:
X (VWx) = slot number × 64 + input channel number × 2
The slot number corresponds to the module's installation location, with the first extension slot next to the CPU being 0, the second extension slot being 1, and so on. There are 8 input channels, from A to G, and the corresponding numbers are 0 to 7.
VWxx | Channel 0 | Channel 1 | Channel 2 | Channel 3 | Channel 4 | Channel 5 | Channel 6 | Channel 7 |
Slot 0 | VW0 | VW2 | VW4 | VW6 | VW8 | VW10 | VW12 | VW14 |
Slot 1 | VW64 | VW66 | VW68 | VW70 | VW72 | VW74 | VW76 | VW78 |
Slot 2 | VW128 | VW130 | VW132 | VW134 | VW136 | VW138 | VW140 | VW142 |
Slot 3 | VW192 | VW194 | VW196 | VW198 | VW200 | VW202 | VW204 | VW206 |
Slot 4 | VW256 | VW258 | VW260 | VW262 | VW264 | VW266 | VW268 | VW270 |
Slot 5 | VW320 | VW322 | VW324 | VW326 | VW328 | VW330 | VW332 | VW334 |
Slot 6 | VW384 | VW386 | VW388 | VW390 | VW392 | VW394 | VW396 | VW398 |
Note: Because the offset address of TD2X text display is also in VW0, so If you need to use Td2X text display in your system, please don't put the EM231 8AI×TC module in slot 0, or the TD2X will not work normally. Siemens TD200 text displayer is same as TD2X.