Outdoor Expulsion Drop-out Type Distribution Fuse Cutout Series

China Outdoor Expulsion Drop-out Type Distribution Fuse Cutout Series, Find details about China Fuse Cutout, Cutout from Outdoor Expulsion Drop-out Type Distribution Fuse Cutout Series

Model NO.
ZNF-4
Arc-Extinguishing Medium
Vacuum
Function
Ovp(Overvoltage Protection)
Certification
ISO9001-2000
HS Code
8535100000
Model NO.
ZNF-4
Arc-Extinguishing Medium
Vacuum
Function
Ovp(Overvoltage Protection)
Certification
ISO9001-2000
HS Code
8535100000

Outdoor Expulsion Drop-out Type Distribution Fuse Cutout Series
Condition of Use:
1. The ambient air temperatures within the range of -30 degreeto +40 degree;
2. The altitude above sea level not exceeding 1, 000m; (If the altitude is higher than 1, 000, it needs adjust. )
3. Frequency of the A. C. Power supply not less than 48Hz and not exceeding 52Hz;
4. Earthquake intensity not exceeding 7 degrees;
5. Maximum wind speed not exceeding 35m/s.

Technical Standard:
The technical performance of the products is in confirmed to IEC291, 282.
Type designation ZNF-4
Rated voltagekV10~1515~2724~2727~3333~3636~38
Rated currentkA100200100200100200100200100200100200
Breaking currentA10000120001000012000800010000600080006000800060008000
Impulse voltage (BIL)kV110110125125150150170170170170180180
Power-frequency withstand volltagekV404045456565707070707070
Leakage distancemm250250350350530530700700720720850850
Figure No. fig. 24fig. 25, fig. 26fig. 27fig. 28fig. 29fig. 30